Indirect Release Systems
Pre-Engineered Commercial Kitchen Fire Suppression System
Rotarex Firedetec System
The Rotarex (Firedetec) Pre-Engineered Fire Suppression System provides reliable and efficient protection for commercial kitchen hoods using advanced pneumatic technology.
Key Features:
- Continuous Linear Sensor Tube: Utilizes a proprietary flexible Fire Detection Tubing (FDT) that offers superior detection and activation.
- Flexible and Space-Efficient: More adaptable and cost-effective compared to traditional mechanical or electronic systems.
- Rapid Response: The FDT is installed directly inside the extractor hood, above cooking areas. When a fire occurs, the tube bursts at 175°C, triggering the system.
- Instant Flooding: The depressurization of the tube actuates a pressure differential valve, rapidly releasing a Class F extinguishing agent to flood the cooking area.
- Effective Suppression: The system suppresses the fire quickly, minimizing damage and downtime.
This system ensures prompt and effective fire suppression, providing peace of mind and safeguarding commercial kitchen environments.
Special Features
| Very Fast, reliable fire detection with help of Clean agents | Easy/Flexible Installation | No electricity or moving parts |
| Highly economical |
TECHNICAL SPECIFICATIONS
| MODEL | SPECIFICATIONS | MODEL | SPECIFICATIONS |
|---|---|---|---|
| Extinguishing Agent | (Rotarex) Wet Chemical System | Capacity | 9 Ltr |
| Working Pressure* | 16 bar | Sensor Tube | Grey |
| Sensor Tube Burst Temperature | 175 deg C | Cylinder | SS |
| Valve | Pi-Marking | Cylinder Approvals* | CE |
| System Approvals* | LPCB | Internal Diameter of Tube | 4 mm |
| Outer Diameter of Tube | 6 mm | Height of Cylinder | Approx. 350 mm |
| Diameter of Cylinder | 175 mm | Operating Temperature | 5 Deg C to 65 Deg C |
| Super pressurizing Agent | Dry Nitrogen | Cylinder Thickness | 1.5 mm |